Fan Operation; Thermostat Control - Panasonic WH-ADF0309J3E5CM Service Manual

Table of Contents

Advertisement

15.3 Fan Operation

Fan operation can be set using remote control.
The indoor fan is operated according to remote control setting and to enables air circulation in the room.

15.4 Thermostat Control

Depending on differences between room temperature, setting temperature and outdoor temperature, compressor
operation is decided and starts operation.
If temperature difference matches values shown below, thermostat switches off.
Model
Cool Mode
Dry Mode
15.4.1
Indoor Fan Control
Manual Fan Speed
Operation starts at Hi, Me+, Me, Me- or Lo speed set by remote control.
Auto Fan Speed
When operation start, or shifting to thermostat ON condition from thermostat OFF condition, indoor fan operates
as below.
(1) The indoor fan speed is controlled as shown below during the automatic fan speed.
(2) The fan speed does not change for 3 minutes during cooling operation once it is changed.
15.4.2
Outdoor Fan Control
Outdoor fan motor is operated with variable fan speed depend on compressor frequency and outdoor ambient
temperature. Outdoor fan turns on when compressor starts to operate. But outdoor fan will turns off 30 seconds after
compressor stops to operate.
C
Outdoor Fan
S-71WF3E
0.0°C
0.0°C
●Cooling
Set temp.
Indoor fan speed
O
N
o
m
p
e r
s s
r o
O
N
F
a
30 sec
T
(deg)
+3
+2
+1
Hi
Me
Lo
O
F
F
n
S
p
e
e
d
O
F
F