25.2.9
Abnormal Zone 1 Sensor (- / - / H43)
Malfunction Caused:
1
Faulty connector connection.
2
Faulty buffer tank sensor.
3
Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
Abnormal zone 1 sensor
Check the turn off power check connector connection
Normal?
Check plug out connector from zone 1 connector sub PCB in
the PCB measure resistance of zone 1 sensor characteristic
match?
Defective PCB
Replace PCB
YES
YES
Caution
NO
Poor contact
Correct connection
NO
Defective zone sensor
Defective zone sensor
Replace sensor
255
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.