15. Operation Control (S-71WF3E)
15.1 Cooling Operation
Cooling operation can be set using remote control.
This operation is applied to cool down the room temperature reaches the setting temperature set on the remote
control.
Cooling Operation Time Diagram.
ON
OFF/ON switch
OFF
ON
Thermostat
OFF
Indoor Pipe
Temperature
ON
Compressor
OFF
ON
Outdoor Unit Fan
OFF
ON
Indoor Unit Fan
OFF
Remarks
15.2 Dry Mode Operation
Soft Dry Operation can be set using remote control.
Soft Dry operation is applied to dehumidify the room.
When operation begins, the fan speed is control as follows.
15.2.1
S-71WF3E
A:Fan speed is as set in the remote controller
B:Fan speed is DRY-L during thermostat ON, SSLo during thermostat OFF
(Lo ≥ DRY-L ≥ SSLo)
Thermostat between
OFF/ON > 7 mins
2 mins
Fan Control
Setting Speed
• Remaining Heat Removal
T (deg)
+3.5
+0.5
Set temp. in remote controller
-3.0
Fan speed
204
0°C or lower
10 mins
3 mins
2 mins
1 min
Fan Control
• Freezing Prevention
A
B
A
6°C or higher
1 min