Panasonic WH-ADF0309J3E5CM Service Manual page 148

Table of Contents

Advertisement

12.2.1.6
Setting / Test Operation
Setting
Clock
RC. setting mode (Main/sub, Clock type)
Detailed setting mode (Ventilation fan output
setting, Room temperature sensor, Temperature
display setting)
Clock
1. Press and hold
2. Set day of the week, hour and minute.
RC. setting mode
1. Press and hold the 2 buttons for several seconds
simultaneously.
,
2. Select the Code no.
3. Select the Set data.
The indicator illuminates after blinking.
Press
.
Code
Item
no.
01
Main/sub
02
Clock type
Detailed setting mode
1. Press and hold the 3 buttons for several seconds
simultaneously.
,
,
2. Select the Code no.
3. Select the Unit no.
4. Select the Set data.
The indicator illuminates after blinking.
Press
.
Code
Item
no.
Ventilation fan
31
output setting
Room temperature
32
sensor
Temperature
33
display setting
for several seconds.
Set data
0000
0001
Sub
Main
24 hours
12 hours (AM/PM)
Set data
0000
0001
Not connected
Connected
Main unit
RC
°C
°F
Test operation
Turn on the circuit breaker beforehand, referring to the
operating instructions for the unit. The remote
controller starts.
1. Press and hold
[TEST] display appears. (The unit enters the test
operation mode.)
2. Press
[TEST] is display during the test operation.
3. Press
. Finish the test operation
[TEST] display disappears.
4. Delete the error history.
Press and hold the 2 buttons for several
seconds simultaneously.
,
Information of errors is displayed.
To delete the error history, press
Press
to finish service mode.
Attention
Do not use this mode for purposes other than the
test operation.
(To prevent overload of this units)
Read the installation instructions supplied with the
units.
Any of the Heat, Cool and Fan operations can
only be performed.
Temperature cannot be changed.
The test operation mode is automatically turned
off in 60 minutes. (To prevent continuous test
operation)
Outdoor units do not operate for approx. 3
minutes after the power is turned on or operation
is stopped.
148
for several seconds.
. Perform the test operation.
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

S-71wf3eCu-2wz71ybe5

Table of Contents