Thermo ON/OFF for Heat Pump in Tank Operation:
When tank temperature achieve heat pump OFF condition, refer below condition:
Conditon 1 : Tank Heater ON (Internal Tank Heater)
Heat pump will turn OFF, water pump continue ON and room heater will continue ON if tank temperature below
tank heater thermo ON condition. 3 ways valve will only switch to room side after tank temperature reach tank
heater thermo OFF condition.
Conditon 2 : Tank Heater OFF (Internal Tank Heater)
If tank temperature achieve tank thermo OFF, heat pump turn OFF, water pump turn OFF, heater OFF and 3
ways valve switch to room side.
When tank temperature achieve heat pump ON condition, water pump ON, heat pump ON and heater turn OFF.
Heat pump OFF condition at Tank Mode
Tank temperature > tank water set temperature continuously for 20 seconds after heat pump thermos OFF
o
due to water thermo. (Heat pump turn OFF but water pump continue ON and heater turn ON to achieve tank
set temperature) OR
Tank temperature > tank set temperature + [1°C] for continuously 20 seconds. (Heat pump OFF, water pump
o
OFF, heater OFF and 3 ways valve switch to room side)
Heat pump ON condition at Tank Mode
Tank temperature < tank water set temperature + R/C setting (Tank re-heat temp) (Water pump turn ON OR
o
continue ON, heat pump ON and 3 ways valve switch to tank side or maintain at tank side)
Tank heater control
Internal heater only operates to tank side if Tank heater ON and backup heater is enable.
Internal heater turn ON condition:
Tank temperature < tank set temperature AND
Tank Thermo ON for the Remote Control Set timer AND
20 minutes from previous heater off AND
Internal tank heater selects USE from control panel.
Internal heater turn OFF condition:
Tank temperature > tank set temperature for continuously 15 seconds OR
Mode change or operation is off by control panel.
14.1.7
Heat + Tank Mode Operation
1. 3 ways valve control:
3 ways valve switch to room side during room heat-up interval and switch to tank side during tank heat-
o
up interval. Both modes will switch alternately. Tank mode is the initial running mode of Heat + Tank
mode.
2. Heat pump operation control:
During room heat-up interval
o
Follow normal heating operation.
Switching to tank side depends to below cases:
Case 1:
[Previous switch from tank interval to room interval due to thermo OFF]
Switch to tank heat-up interval when Tank temp < Tank thermos ON temp (Room heat-up interval
ends)
Case 2:
[If heating operation at room side is less than 30 minutes and switch to tank side 3 times
consecutively]
Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND Tank
temperature < Tank thermo ON temperature.
Case 3:
[Previous switch from tank interval to room interval due to tank interval timer is complete]
Maintain at room heat-up interval regardless of the tank temperature. Switch to tank heat-up interval
only when (Room Interval Timer is complete OR Room heat pump thermo OFF) AND tank
temperature < Tank thermo ON temperature.