16.1.3
Outdoor Cooling Quiet Operation Control
Purpose
Provide quiet cooling operation when only 1 indoor in operation.
Start Condition
Indoor fan speed is lower than Lo fan.
o
Only 1 operation indoor unit.
o
Not in any cooling overload zone.
o
Not during annual cooling
o
Not initial frequency operation.
o
Not during starting control.
o
During cool mode
o
Not in Heat Recovery mode.
o
All conditions above are satisfied and function selection enable.
Control Contents
Compressor frequency and outdoor fan speed maximum limit is set. Adjust accordingly.
Cancel Condition
Indoor fan speed is equal or higher than Lo fan.
o
> 1 operation indoor unit.
o
In any cooling overload zone.
o
During annual cooling
o
Initial frequency operation.
o
During starting control.
o
Not during cool mode
o
When any above is satisfied
208