Configure Pressure Loop
Settings
The PCF system uses variables (Kp and Ki) in the soft-
ware calculations to accurately and precisely control the
fluid pressure.
NOTE: It is recommended that these values not be
changed from the factory defaults of 32.00 for Kp
and 128.00 for Ki. However, if the values need to be
adjusted, see Verify Flow Meter Calibration on page
38.
32
to enter the
to enter the value.

Adjust Pressure Sensors

Set pressure offsets and pressure limits.
NOTE: Inlet sensor settings will be grayed out on
this screen for systems with heated fluid plates.
1. With the system in setup mode, navigate to the Fluid
Plate set of screens.
2. Press
to scroll to the Pressure Sensors
screen (screen 5).
3. Press
to access the fields to make changes.
F
. 26
IG
NOTE: For the following steps, press
and
to navigate through each field, and
to open drop-down menus and enter changes
or selections.
4. Set the desired offset for the inlet and outlet pres-
sures between 0 and 100 psi (0.7 MPa, 7.0 bar).
Remove all pressure on the sensors, and then
adjust the offset so the measured value reads 0.
NOTE: It is recommended that offsets should not be
changed from the factory defaults of 0.