Graco PCF Instructions And Parts page 25

Precision dispense system
Table of Contents

Advertisement

Module Status (MS)
State
Description
Off
Not initial-
ized
Green
Normal
operation
Flashing
Initialized,
Green
diagnostic
event(s)
present
Red
Exception
error
Red (1
Configura-
flash)
tion error
Red (2
IP Address
flashes)
not set
Red (3
Station
flashes)
Name not
set
Red (4
Major Inter-
flashes)
nal Error
Link/Activity (Link)
State
Off
No Link, no communication present
Green
Link established, no communication present
Green,
Link established, communication present
flashing
313377B
Comments
No power or module in
"SETUP" or "NW_INIT" state
Diagnostic event(s) present
Used by engineering tools to
identify node on network
Module in state "EXCEPTION"
Expected Identification differs
from Real Identification
Set IP address via system
monitor or DNS server
Set Station Name via system
monitor
Cycle system power; replace
module
Description
EtherNet/IP
NS
F
. 17: EtherNet/IP Fieldbus Connections
IG
The Ethernet interface operates at 100Mbit, full duplex,
as required by PROFINET. The Ethernet interface is
auto polarity sensing and auto-crossover
Network Status (NS)
State
Off
No power or no IP address
Green
On-line, one or more connections established
(CIP Class 1 or 3)
Flashing
On-line, no connections established
Green
Red
Duplicate IP address, FATAL error
Flashing
One or more connections timed out (CIP Class
Red
1 or 3)
Module Status (MS)
State
Off
No power
Green
Controlled by a Scanner in Run state
Flashing
Not configured, or Scanner in Idle state
Green
Red
Major fault (EXCEPTION-state, FATAL error
etc.)
Flashing
Recoverable fault(s)
Red
LINK/Activity (Link)
State
Off
No link, no activity
Green
Link established
Flashing
Activity
Green
Installation
MS
Link
TI11814A
capable.
Description
Description
Description
25