Omron H3CR-A Manual page 309

Hide thumbs Also See for H3CR-A:
Table of Contents

Advertisement

H3BF
Ratings
Rated supply voltage
Operating voltage range
Power consumption
Control outputs
Characteristics
Accuracy of operating time
Setting error
Reset time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Approved standards
Weight
Note: When the timer is set at a rated time of 0.5 s or 1 s, add !10 ms to the respective characteristics.
Engineering Data
Load current (A)
100/110/120 or 200/220/240 VAC (50/60 Hz)
24, 48, 100 or 110 VDC (permissible ripple: 20% max.)
85% to 110% of rated supply voltage
AC: approx. 10 VA/2 W; DC: approx. 1 W
5 A at 250 VAC, resistive load (cos% = 1)
Minimum permissible load (ref. value): 10 mA at 5 VDC
!0.3% (see note)
!5%
0.1 s max.
!0.5% (see note)
!2% max. (see note)
100 M$ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts and
between contact and control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
2
Destruction: 1,000 m/s
(approx. 100G)
2
Malfunction: 100 m/s
(approx. 10G)
Operating: --10"C to 55"C
Operating: 35% to 85%
Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
See "Engineering Data."
UL (File No. E41515), CSA (File No. LR22310)
Approx. 100 g
H3BF
309

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents