Omron H3CR-A Manual page 296

Hide thumbs Also See for H3CR-A:
Table of Contents

Advertisement

H3BH
Ratings
Rated supply voltage
Operating voltage range
Power consumption
Control outputs
Note: When power is applied to any of the H3B series Timers, an initial current of approx. 0.3 A flows for approx. 1 s (M series), 0.1 s (S
series), irrespective of the rated supply voltage of the Timer.
Characteristics
Accuracy of operating time
Setting error
Power ON time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Approved standards
Weight
Note: 1. When the Timer is set at a rated time of 0.5 s or 1 s, add !10 ms to the respective characteristics.
2. Resetting time means the minimum power application time for power OFF-delay Timer.
If less, the output relay may not release.
Engineering Data
Load current (A)
296
100/110/120 or 200/220/240 VAC (50/60 Hz);
24, 48, 100, or 110 VDC (permissible ripple: 20% max.)
85% to 110% of rated supply voltage
AC: approx. 0.5 VA; DC: approx. 0.7 W
5 A at 250 VAC, resistive load (cos% = 1)
Minimum permissible load (ref. value): 10 mA at 5 VDC, 100 mA at 5 VDC (-8R)
!0.3% (see note 1)
!5%
S series: 0.1 s min.
M series: 2 s min.
!0.5% (see note 1)
!2% max. (see note 1)
100 M$ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts and
between contact and control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
2
Destruction: 1,000 m/s
(approx. 100G)
2
Malfunction: 100 m/s
(approx. 10G)
Operating: --10"C to 55"C
Operating: 35% to 85%
Mechanical: 10,000,000 operations min. (under no load at 1,200 operations/h)
Electrical:
See "Engineering Data."
UL (File No. E41515), CSA (File No. LR22310)
Approx. 100 g
H3BH