Setting up the interval for sequential start/stop

This function prevents all management points to be started or stopped at once when start/stop is
ordered for an area by sequentially starting or stopping its member management points and areas
in the order they are listed in the Area Member Registration screen.
1. Touch the Modify buttons
starting or stopping in the Numerical Input dialog box that appears. The range of values you can
specify is 0 to 180 seconds.
Area1
Starting interval: 2 sec
127
(15)
(16)
and
on the Area Attribute Setup screen. Enter the interval for
ON after 0 sec
2-sec interval
ON after 2 sec
2-sec interval
ON after 4 sec
2-sec interval
ON after 6 sec
User's Manual EM11A015B
intelligent Touch Manager
(15)
(16)
··· Area
··· Management point