• Simultaneous status change effects
In the event where input conditions becomes true for output 1 and output 2 simultaneously and
the target of both outputs is the same with opposite On and Off the function may temporarily
show unexpected behavior.
Example:
When the program is set as follows.
Input: 1-00, 1-01
Required duration: 0 min
1-00
Operating
On
Stopped
Off
1-01
Operating
On
Stopped
Off
1-02
Operating
On
Stopped
Off
161
Output 1: One input status change → 1-02 turns ON
Output 2: All inputs status change → 1-02 turns OFF
When 1-02 ON or 1-02 OFF is detected on controller
(Output 1: One condition is true), 1-02 may transiently
output ON signal.
User's Manual EM11A015B
intelligent Touch Manager
Output 1 and Output 2 conditions are
true simultaneously.