Condition to detect
Required duration*2
Switch
Specify the time
during which the
Equipment error
required condition is
Analog upper/lower
continuously cleared
limit error
in the 0 to 30
minutes range, in
Operation mode
increments of 1
minute.
Specify the time
during which the
required condition is
continuously cleared
Analog value
in the 1 to 30
minutes range, and
in increments of
1 minute.
*2 For the explanation of the required duration, see "Example: Delay ON timer (15 min. example)" on the
next page.
Example: If required duration is set to "15 minutes"
whether the "condition has been cleared" is assessed only after 15 minutes, and not when
the monitored target reached the specified status.
The figure below shows the example of an assessment when the required condition is
"On" and required duration, "15 minutes".
On/Off status
On (Success)
Switch
success/failure
Off (Failure)
Success
Required duration
cleared/not cleared
Failure
Success when
simultaneously cleared
Success
Success
assessment
Failure
Specify which will be considered condition cleared: On or
error, or Off or normal.
* On/Off, or error/normal must be set on the management
point side.
Specify which operation mode clears the condition.
Specify the analog value that clears the condition as an
expression.
On
15 minutes
Condition is considered
cleared when On status
continues for required dura-
tion
Condition is considered not
cleared when Switch fails (Off)
User's Manual EM11A015B
intelligent Touch Manager
Required condition
Status
Off
On
Off
Time
15 minutes
15 minutes
Condition is not cleared because
Switch succeeded (On) but failed
(Off) before the required duration
has elapsed
158