Daikin DCM601A51 User Manual page 111

Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

When the thermal difference is 2°C
• When Representative suction temperature – Representative setpoint (Heat) > Thermal difference + 0.5,
operation mode is changed from Heat to Cool
• When Representative setpoint (Cool) – Representative suction temperature > Thermal difference + 0.5,
operation mode is changed from Cool to Heat
Representative setpoint (Heat) +
Thermal difference in (2°C) + 0.5
Representative setpoint (Cool)
Representative setpoint (Heat)
Representative setpoint (Cool) –
Thermal difference in (2°C) – 0.5
When the thermal difference is 1°C
• When Representative suction temperature – Representative setpoint (Heat) > Thermal difference + 1,
operation mode is changed from Heat to Cool
• When Representative setpoint (Cool) – Representative suction temperature > Thermal difference + 1,
operation mode is changed from Cool to Heat
Representative setpoint (Heat) –
Thermal difference in (1°C) + 1
Representative setpoint (Cool)
Representative setpoint (Heat)
Representative setpoint (Cool) –
Thermal difference in (1°C) –1
Heating mode
Cooling mode
°C
Representative
suction temperature
Cooling mode
Heating mode
<When the thermal difference is 2°C>
Heating mode
Cooling mode
°C
Representative
suction
temperature
Heating mode
<When the thermal difference is 1°C>
User's Manual EM11A015B
intelligent Touch Manager
Heating mode
Cooling mode
Cooling mode
Heating mode
Cooling mode
3°C
0.5°C
2°C
0.5°C
Heating mode
3°C
1°C
1°C
1°C
Heating mode