The step above finishes the setup of Output2 for the program, "which turns off Ventilator "c"
when both indoor units "a" and "b" go off".
The "Ventilator control program" is now complete.
Touch the OK button and return to the main Interlocking Control screen.
• Enabling the Interlocking Program
Enable the created interlocking program.
Select "Ventilator control program" and select the Enable radio button (24).
Check that the Activation column of the list is set to Enable and touch the Close button to close
the screen.
User's Manual EM11A015B
intelligent Touch Manager
(24)
170