• Dio, Ao, Mo Tab
Sets up the Dio, Ao and Mo.
Change settings by selecting the relevant check boxes.
(1)
Dio
Enable/disable Repeat Mode for Dio, and select and set up a repetition interval in the 1 to
10-minutes range, in increments of 1 minute.
When the Repeat Mode is enabled, a start/stop attempt will be repeated again at the specified
repetition interval.
(2)
Ao
Ao refers to analog signal output.
This function enables the signal output equipment (I/O module) connected to the iTM to output a
current/voltage corresponding to the adjustment value from external equipment.
(It is used for the adjustment of building equipment, such as degree of aperture of a damper/valve.)
The range, incremental width, and unit of the analog values are set on the screen during trial.
(The unit setting may not be available.)
Ao control image (Example: Changing the degree of damper aperture)
(1) On the iTM, set the degree of aperture (analog value).
(2) A voltage corresponding to the analog value is output from the I/O module.
(3) The damper aperture is set according to the input voltage.
(1)
(3)
iTM
(3) Damper
(1) Ao Setting
Set to 50% aperture
Set degree of aperture
according to input
to 50 (%).
voltage.
User's Manual EM11A015B
intelligent Touch Manager
(2)
(2) I/O module
I/O module
Voltage output
Damper
Valve
50