The equipment does not operate according to the schedule although the set time/date has
arrived.
Cause (1)
• The target equipment is under maintenance.
Checking method
• Check if the target equipment icon on the centralized monitoring screen shows the under
maintenance status.
Measure
• Commands cannot be sent to equipment under maintenance. When maintenance is
completed, clear the equipment under maintenance status from System Settings.
Cause (2)
• The target equipment is in an emergency stop state.
Checking method
• Check the Emergency icon displayed on the centralized monitoring screen.
Measure
• Operation commands cannot be sent to equipment in an emergency stop state.
Cause (3)
• A power failure occurred.
Checking method
• Use the iTM's Schedule function to check if "Start Up" remains after the scheduled date/time.
Measure
• Commands cannot be sent to equipment during a power failure.
File output to a USB memory fails.
iTM provides multiple functions such as Backup and Setup Export for outputting files to a
connected USB memory.
Check the following items if file output to a USB memory fails.
• Free space of the destination USB memory is not enough.
Check free space of the USB memory. (5 GB or more is recommended)
• The destination USB memory is write protected.
Unlock the write protection before use.
For how to unlock, see the instruction manual or etc, of the USB memory used.