• Similarly, two analog values are compared as follows.
Example: [Analog value at the management point > Analog value at the management point + Offset ± Hysteresis]
Analog value at management point (1) >
Analog value at management point (2) + Offset + Hysteresis
Analog value at management point (1) <
Analog value at management point (2) + Offset – Hysteresis
Except above
Analog value
Assessment interval (1 minute)
Assessment interval (1 minute)
Assessment
Success
Failure
Example: [Analog value at the management point < Analog value at the management point + Offset ± Hysteresis]
Analog value at management point (1) <
Analog value at management point (2) + Offset – Hysteresis
Analog value at management point (1) >
Analog value at management point (2) + Offset + Hysteresis
Except above
Analog value
Assessment interval (1 minute)
Assessment interval (1 minute)
Assessment
Success
Failure
Range condition can be defined by combining the two cases above.
Analog value at management point (2)
Analog value at management point (2)
Analog value at management point (1)
Analog value at management point (1)
Analog value at management point (2)
Analog value at management point (2)
Analog value at management point (1)
Analog value at management point (1)
User's Manual EM11A015B
intelligent Touch Manager
Success
Failure
Not assessed (Previous assessment kept)
Management point (2) + Offset
Management point (2) + Offset
Success
Failure
Not assessed (Previous assessment kept)
Management point (2) + Offset
Management point (2) + Offset
Hysteresis
Hysteresis
Offset
Offset
Time
Hysteresis
Hysteresis
Offset
Offset
Time
Time