[Chiller]
Output D3Chiller data items
No.
Item
Operation time of heating
1
(Total)
Operation time of cooling
2
(Total)
3
Start/Stop count
Inlet Water Temp.
4
(Average)
Inlet Water Temp.
5
(Maximum)
Inlet Water Temp.
6
(Minimum)
Outlet Water Temp.
7
(Average)
Outlet Water Temp.
8
(Maximum)
Outlet Water Temp.
9
(Minimum)
*Room temperature is output in Celsius or Fahrenheit depending on the System Settings.
[Dio]
Output Di/Dio data items
No.
Item
1
Operation time (Total)
2
Start/Stop count
[Pulse]
Output Pi data items
No.
Item
1
Meter value (Total)
[Analog]
Output Ai data items
No.
Item
1
Analog value (Average)
341
The data is rounded to within the output effective range if it is outside the range.
Collection method
Accumulated operating time (in minutes)
of the DIII Chiller in heating mode
Accumulated operating time (in minutes)
of the DIII Chiller in cooling mode
Number of times DIII Chiller has been in
operation.
15-minute average of 1-minute data over
1-hour (data collection time)
Maximum 1-minute value
in 1-hour (data collection time)
Minimum 1-minute value
in 1-hour (data collection time)
15-minute average of 1-minute data over
1-hour (data collection time)
Maximum 1-minute value
in 1-hour (data collection time)
Minimum 1-minute value
in 1-hour (data collection time)
Collection method
Accumulated Di/Dio operation
time, in minutes
Number of times Di/Dio has been in
operation.
Collection method
Hourly (data collection time) total
Collection method
15-minute average of 1-minute data over
1-hour (data collection time)
User's Manual EM11A015B
intelligent Touch Manager
Unit
Valid output range
Minutes
0≤Value≤60
Minutes
0≤Value≤60
Times
0≤Value≤9999
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
˚C *
–50.0≤Value≤120.0 *
˚F *
–58≤Value≤248 *
Unit
Valid output range
Minutes
0≤Value≤60
Times
0≤Value≤9999
Unit
Valid output range
-
0≤Value≤999999.99
Unit
Valid output range
–100000.0≤Value
-
≤100000.0