Cautions when Using Simultaneously with Other Control Functions
1. This function cannot control indoor units that are already under control of the Heating Mode
Optimization function.
2. If the Timer Extension function is set up for an indoor unit where this function is enabled, the
indoor unit may be started again by this function after being stopped by the Timer Extension
function.
3. When used together with the Sliding Temperature function, the indoor unit may be repeatedly
started and stopped every 5 minutes (hunting) depending on the setpoint.
Example: When the setpoint for Sliding Temperature calculated from the outdoor temperature is
32°C and the upper limit for this function is 32°C.
1. When the room temperature exceeds 32°C, this function orders cooling to start.
2. The cool setpoint is set to 32°C by the Sliding Temperature function.
3. When the room temperature drops below 32°C, since room temperature < cool setpoint,
this function orders cooling to stop.
4. The room temperature exceeds 32°C, and this function orders cooling to start. (Back to
1.)
When Using this Function
Use the target indoor units with automatic recovery from power failure set to "OFF".
Be sure to consult a service person before using.
User's Manual EM11A015B