Touching the Delete button
(14)
deletes the selected day of the week operation rule.
Touching the Edit button
(15)
displays the Operation Rule screen that allows you to edit the
selected day of the week operation rule.
(18)
(a)
(16)
(b)
(c)
(17)
(16)
is the list of registered operation rules with operating hours and setpoint details.
Selecting an operation rule and touching the Delete button
(17)
deletes the selected operation
rule.
Utilize Hours and Setpoints in (18).
Enter the Start Time and End Time in Utilize Hours. Touch the Modify button and enter the times
in the Time Setup dialog that appears.
You can set up in the 00:00 to 24:00 (AM00:00 to PM12:00 when using 12-hour clock) range,
and in increments of 15 minutes. If the entered value is not a multiple of 15 minutes, a dialog is
displayed and the value rounded to a multiple of 15 minutes.
In addition, you cannot set hours spanning two days.
Select the check box
(a)
if applying a setpoint to the utilize hours.
You can set temperatures for both cooling and heating. To enter a temperature, select the check
box and touch the Modify button to display the Numerical Input dialog.
You can enter values in the –30 to 70°C range, in increments of 0.1°C.
Touch the Add button
(b)
to add the new setting to (16).
You can set up to 10 operating hours to one operation rule.
To change the settings, you can select an existing operation rule from (16), enter new settings for
it in (18), and then touch the Modify button (c).
Touch the OK button to return to the Operation Rule Setup screen.