INSTALLATION INSTRUCTIONS SPLIT SYSTEM AIR CONDITIONER (R-410A) INSTALLATION & SERVICE REFERENCE CONDENSING UNIT EVAPORATIVE UNIT MODELS MODELS FDMRN20AVAK RR20AVAK9/DX16SA0181XM RR25AVAK9/DX16SA0241XM FDMRN25AVAK RR30AVAK9/DX16SA0301XM FDMRN30AVAK RR36AVAK9/DX16SA0361XM FDMRN36AVAK RR42AVAK9/DX16SA0421XM FDMRN42AVAK Our continuing commitment to quality products may mean a change in specifications without notice.
Specification sheets can be found at www.daikin-ksa.com or www.daikincomfort.com for Daikin. Within the website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
Page 3
1.5TR 2.5TR 3.5TR Outdoor Model RR20AVAK9 RR25AVAK9 RR30AVAK9 RR36AVAK9 RR42AVAK9 Indoor Model FDMRN20AVAK FDMRN25AVAK FDMRN30AVAK FDMRN36AVAK FDMRN42AVAK (*1) Btu/h 18,000 23,000 28,000 34,000 39,000 Actual Cooling Capacity T1 5.27 6.74 8.20 9.96 11.43 (*2) 16,500 21,000 24,000 29,000 33,000 Btu/h Actual Cooling Capacity T3 4.83...
Installation Clearances Special consideration must be given to location of the condensing unit(s) in regard to structures, obstructions, other units, and any/all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an obstruction there should be a minimum of 1.52 meters (60 inches) between the top of the unit and the obstruction(s).
Refrigerant Lines Use only refrigerant grade (dehydrated and sealed) copper tub- To avoid possible explosion: ing to connect the condensing unit with the indoor evaporator. • Never apply flame or steam to a refrigerant cylinder. If you After cutting the tubing, install plugs to keep refrigerant tubing must heat a cylinder for faster charging, partially immerse clean and dry prior to and during installation.
Refrigerant Line Connections IMPORTANT VALVE PISTON CONNECTOR This outdoor unit comes with a factory-installed COMPONENT flowrator which is part of the service valve as- sembly. The flowrator piston is located within a connector tube (Figure 4) which is torqued to the service valve body.
CAUTION Prolonged operation at suction pressures less than 138 K a 20 psig) for more than 5 seconds will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal. To avoid the risk of fire or explosion, never use oxygen, high NOTE: Scroll compressors should never be used to evacuate or pressure air or flammable gases for leak testing of a refrigeration pump down a heat pump or air conditioning system.
Overcurrent Protection NOTICE The following overcurrent protection devices are approved for Units with rotary or reciprocating compressors and non-bleed use. TXV’s require a Hard Start Kit. • Time delay fuses • HACR type circuit breakers These devices have sufficient time delay to permit the motor-compressor to start and accelerate its load. Three Phase Compressor Rotation CAUTION Three phase compressors are power phase dependent and can...
1. 3/8” valve to 5 - 10 in-lbs 0.56-1.30 Nm CAUTION 2. 5/8” valve to 5 - 20 in-lbs 0.56-2.26 Nm POSSIBLE REFRIGERANT LEAK 3. 3/4” valve to 5 - 20 in-lbs 0.56-2.26 Nm To avoid a possible refrigerant leak, open the service valves until 4.
Troubleshooting Information COOLING ANALYSIS CHART System Operating Complaint No Cooling Unsatisfactory Cooling Pressures POSSIBLE CAUSE Test Method DOTS IN ANALYSIS Remedy GUIDE INDICATE "POSSIBLE CAUSE" Power Failure · Test Voltage Blown Fuse · · · Impact Fuse Size & Type Loose Connection ·...
SPLIT SYSTEMS AIR CONDITIONING AND HEAT PUMP HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a qualified servicer. REPLACE OR CLEAN FILTER IMPORTANT NOTE: Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire.
Page 15
2 - EVAPORATIVE UNIT Important Safety Instructions & Precautions When installing the unit, adhere to the following impor- tant points: • DO NOT INSTALL the unit where leakage of flammable HIGH VOLTAGE! gas may occur. Disconnect ALL power before servicing. Multiple power sources may be present.
Unpacking the Evaporative Unit Carton Box UNPACKING: 1. After taking off the bands, lift carton box. 2. Remove the top cushion. Top Cushion 3. Lift the unit and remove the bottom carton. Indoor Unit Packing Bottom Figure 6 Dimensions Figure 7 Dimensions in mm Model FDMRN20AVAK...
Installation Diagram Cork Tape Fully Insulated Indoor Unit Insulation for Indoor Connecting Pipe Figure 8 Installation of the Indoor Unit The indoor unit must be installed so there is no short circuit of the cool discharge. Respect the See Detail A Insulation material installation clearances.
Page 18
• Ensure that the ceiling is structurally sufficient to withstand the weight of the suspended unit. Center distance of axle, see Figure 10. A mm L mm Model (inch) (inch) FDMRN20AVAK 1072 FDMRN25AVAK (21.5) (10.1) FDMRN30AVAK FDMRN36AVAK 1336 FDMRN42AVAK (52.2) (10.1) Figure 10 300mm...
Page 19
Ceiling Concealed Drain Piping Work Bottom of the unit Drain trap Do not leave in water Insulate securely Unit: mm Figure 12 • To avoid damage caused by leaks and condensation, the drain pipe must be installed as shown in Figure 12. •...
Page 20
• Insert the flare nuts mounted on the connection parts of both indoor Figure 14 and outdoor unit into the copper pipes. Flared Tube Flare Joint • The exact length of pipe protruding from the face of the swaging block is determined by the flaring tool.
• Over-tightening can damage the terminal screws. • Do not connect wires of different gauge to same terminal. • Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover. Connect wires of the Do not connect wires of the Do not connect wires same gauge to both side.
3. Connect the charging gauge to the service port of the 3-way CAUTION valve. POSSIBLE REFRIGERANT LEAK 4. Start the vacuum pump. Using a micron gauge, evacuate If the gauge needle does not move to -760mmHg, use a the system for a minimum of 250 microns and wait for 5 refrigerant detector at the flare type connection of the indoor and minutes to ensure the readings will not change.
Service and Maintenance Service Parts Maintenance Procedure Period Remove any dust on the filter by using a vacuum cleaner or At least once every two weeks. wash in lukewarm water (below 40°C) with neutral cleaning Clean more frequently if detergent. necessary.
Page 24
Wiring Diagram HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 25
APPENDIX - LONG LINE SET APPLICATION R-410A...
ATTENTION INSTALLING PERSONNEL As a professional installer you have an obligation to know the product better than the customer. This includes all safety precau- tions and related items. Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
SECTION 1. GENERAL REQUIREMENTS FOR ALL LONG LINE SET APPLICATIONS Equivalent length must be used to determine acceptability of any long line set application. See Section 5 for equivalent length calculations. For any residential split system installed with a long line set, 3/8” liquid line size must be used. Limiting the liquid line size to 3/8”...
Page 28
Hanger Wall Liquid Line Stud Strapped to Suction Line Liquid Line Metal Sleeve Suction Line ® Wrapped in Armaflex Figure 1-1. Installation of Refrigeration Piping From Vertical to Horizontal IMPORTANT - Refrigerant lines must not touch wall. Suction Line Liquid Line Outside Wall Wood Block Between Studs...
If hanging line set from a joist or rafter, use metal strapping or heavy nylon wire tires Wire Tie that are securely anchored. (around suction line only) 8’ (2.4 m) Floor Joist or T ape or Wire Tie Roof Rafter 8’...
An accumulator is not required for air conditioners (accumulators are factory installed on heat pumps). An oil trap at the indoor unit is not required. Liquid Line Solenoid not required if non-bleed TXV is used on the outdoor unit. SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNIT Accessory Air Conditioner (AC) Heat Pump (HP)
SECTION 4. OUTDOOR UNIT IS BELOW THE INDOOR UNIT Accessory Air Conditioner (AC) Heat Pump (HP) Crankcase Heater (40 watts minimum) Hard Start Assist (See manual for each product) (See manual for each product) TXV (Indoor) Liquid Line Solenoid at Outdoor Yes *See Note 5 (Kit # LSK02*) Inverted Refrigerant Trap at Indoor...
SECTION 5. CALCULATIONS - TUBING EQUIVALENT LENGTH, TUBE SIZE AND REFRIGERANT In long line applications the “equivalent line length” is the sum of the straight length portions of the suction line plus losses (in equivalent length) from 45 and 90 degree bends. Add the total straight (lineal) length of tubing to the equivalent length of elbows and bends to get total equivalent length.
Page 34
Refrigerant Quantity Adjustment. All residential R-410A outdoor units are factory charged for 15 feet (4.6 m) of line set. To calculate the initial amount of extra refrigerant (in ounces): a. Subtract 15 feet (4.6 m) from the total linear (not equivalent) length of actual line set b.
Page 36
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE Quality Makes the Difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have designed these units to significantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate.
Page 37
تعليمات التركيب )R-410a( مك ي ّ ف هواء بنظام سبليت مرجع التركيب والخدمة وحدة التبخير وحدة التكثيف الطرازات الطرازات FDMRN20aVaK RR20aVaK9/DX16Sa0181XM FDMRN25aVaK RR25aVaK9/DX16Sa0241XM FDMRN30aVaK RR30aVaK9/DX16Sa0301XM FDMRN36aVaK RR36aVaK9/DX16Sa0361XM RR42aVaK9/DX16Sa0421XM FDMRN42aVaK .قد يتم إجراء بعض التغييرات في المواصفات دون إخطار من منطلق التزامنا المستمر بالحفاظ على جودة المنتجات...
Page 38
التشغيل. ويتم تقييم األداء عند التدفق المحدد للهواء. انظر ورقة مواصفات الوحدة الخارجية لطرازات نظام السبليت أو ورقة مواصفات المنتج للطرازات . الرجاء تحديدwww.daikincomfort.com أوwww.daikin-ksa.com على الموقعDaikin التجارية المعبئة والخفيفة. يمكن العثور على أوراق مواصفات قائمة المنتجات سواء السكنية أو التجارية في المواقع، ثم حدد القائمة الفرعية لنوع المنتج المراد تركيبه، مثل مكيفات الهواء أو مضخات الحرارة، للوصول...
Page 40
خلوص التركيب يجب إعطاء اهتمام خاص بموقع وحدة أو وحدات التكثيف فيما يتعلق بالمباني والعوائق والوحدات األخرى وأي من العوامل األخرى أو جميعها التي قد تتداخل مع دورة الهواء. ينبغي أن يكون الجزء العلوي من الوحدة بدون أي عوائق قدر اإلمكان؛ لكن، إذا كانت ظروف التركيب العمودي ...
Page 41
وصالت المبرد استخدم فقط األنابيب النحاسية الخاصة بالتبريد (مجففة ومغلقة) لتوصيل وحدة التكثيف مع المبخر الداخلي. بعد قص األنابيب، قم بتركيب سدادات للحفاظ على أنابيب التبريد نظيفة وجافة قبل التركيب وأثناءه. ينبغي دائم ً ا أن يتم قطع األنابيب بشكل مربع مع إبقاء النهايات دائرية وخالية من .النتوءات.
Page 42
توصيالت وصلة التبريد هام مكون المك ْ بس الصمام الموصل )flowrator( تأتي هذه الوحدة الخارجية مع الفلوراتر المركب من المصنع الذي يعد جز ء ً ا من مجموعة صمام ) داخل أنبوبflowrator( الصيانة. يقع مكبس الفلوراتر .موصل (الشكل 4) الذي يطوق جسم صمام الصيانة ومن...
Page 43
تفريغ النظام .يتم إغالق صمامات السائل والشفط بوحدة التكثيف إلبقاء الشحن داخل الوحدة .يتم شحن الجهاز من المصنع بعد تركيب سدادات الصمامات وتركيب األغطية .ال تفتح الصمامات حتى يتم تفريغ النظام مالحظة: ينبغي عدم استخدام ضواغط حلزونية لتفريغ أو ضخ في مواد في .المضخة...
Page 44
الحماية من التيار الزائد .تمت الموافقة على استخدام أجهزة الحماية من التيار الزائد التالية منصهرات تأخير الوقت • HACR القواطع الكهربائية من نوع • هذه األجهزة تؤخر الوقت على النحو الذي يسمح لضاغط المحرك بالبدء .وتسريع حمولته دوران الضاغط ثالثي المراحل تعتمد...
Page 45
ال تدخل غاز التبريد المبرد من االسطوانة إلى علبة مرافق الضاغط فقد يتسبب .ذلك في تلف الضاغط .قم بتفريغ الضغط عبر فتح صمامي قاعدة الشفط والسائل بالكامل اضبط الثرموستات لبدء التبريد. افحص تشغيل المروحة الداخلية والخارجية واسمح للنظام أن يستقر لمدة 01 دقائق لطراز الفتحات الثابتة و02 دقيقة .لصمامات...
Page 50
أنظمة سبليت توصيات الصيانة الدورية لمالك مضخة تكييف الهواء والحرارة .نوصي بشدة أن ي ُ جرى فحص صيانة نصف سنوي من قبل فني صيانة مؤهل قبل بدء مواسم البرودة والحرارة. بواسطة فني مؤهل االستبدال أو فلتر التنظيف مالحظة هامة: ال تقم بتشغيل الوحدة بدون تركيب فلتر فقد يتسبب ذلك في تجمع األتربة والنسالة على األجزاء الداخلية للوحدة مما يؤثر سل ب ً ا على كفاءة التشغيل وتلف .الجهاز...
Page 51
2 – وحدة التبخير احتياطات وتعليمات هامة للسالمة :عند تركيب الوحدة، التزم بالنقاط المهمة التالية تجنب تركيب الوحدة في األماكن التي يمكن أن يحدث بها تسرب • .للغازات القابلة لالشتعال في حالة تسرب الغاز وتجمعه حول الوحدة، فإن ذلك قد يسبب .اشتعال...
Page 53
مخطط التركيب 8 الشكل تركيب الوحدة الداخلية يجب تركيب الوحدة الداخلية بحيث ال توجد دائرة قصور .لتفريغ الهواء البارد. التزم بتصاريح التركيب تجنب تركيب الوحدة الداخلية في أماكن تتعرض فيها الوحدة ألشعة الشمس المباشرة، ويجب أن يكون المكان مناس ب ً ا لتوصيل...
Page 54
.10 مسافة توسيط المحور، انظر الشكل اترك مسافة فارغة لتسهيل الصيانة ولتدفق الهواء على النحو 10 الشكل .11 األمثل كما هو موض ّ ح في الشكل 11 الشكل...
Page 55
عمل أنبوب التصريف المخفي بالسقف 12 الشكل .يجب تركيب أنبوب التصريف على النحو الموض ّ ح في الشكل 21 لتجنب الضرر الذي تسببه التسريبات والتكثيف • .للحصول على أفضل نتيجة؛ احرص على أن يكون األنبوب قصي ر ً ا قدر اإلمكان. قم بإمالة األنبوب بزاوية لتحسين التدفق •...
Page 56
14 الشكل توصيل األنابيب بالوحدتين قم بمحاذاة وسط األنبوب واربط الصامولة المعدنية بإحكام باستخدام أصابعك. انظر • .14 الشكل اربط الصامولة المعدنية باستخدام أحد مفاتيح العزم حتى يطقطق المفتاح. عند ربط • الصامولة المعدنية باستخدام مفتاح العزم، تأكد من ربطها في اتجاه السهم الموجود .على...
Page 57
16 الشكل R-410a احتياطات خاصة عند استخدام وحدة أحد غازات التبريد من نوع الهيدروفلوروكربون، وهوR-410A يعد • ال يلحق الضرر بطبقة األوزون. ويصل ضغط تشغيل غاز التبريد هذا ). يجب تركيبR-22( إلى 6.1 ليتخطى ضغط غاز التبريد التقليدي . وصيانتها على نحو سليمR-410A وحدات ي...
Page 58
مصابيح المؤشرات تشخيص األخطاء .إذا تم الكشف عن حالة غير طبيعية، ستومض وحدة التحكم برمز الخطأ مالحظة: لن تكتشف الوحدة المستشعر المفقود عند تشغيل الضاغط. اتصل .بالموز ّ ع الذي تتعامل معه على الفور عند وقوع هذا الخطأ قائمة المراجعة :تأكد...
Page 60
مخطط التوصيالت الكهربائية ﺑﻨﻔﺴﺠﻲ ﺑﺮﺗﻘﺎﻟﻲ ﺑﻨﻲ ﻭﺭﺩﻱ ﺃﺣﻤﺮ ﺑﻨﻔﺴﺠﻲ ﺗﻜﻤﻴﻠﻲ .التوصيالت الكهربائية عرضة للتغيير. فاحرص دائم ا على الرجوع إلى مخطط التوصيالت الكهربائية بالوحدة لمعرفة أحدث التوصيالت الكهربائية...
Page 61
410a-R الملحق - استعمال مجموعة الوصالت الطويلة ألجهزة التكييف...
Page 62
تنبيهات مهمة لفني التركيب .كفني تركيب محترف، يتعين عليك معرفة المنتج بشكل ٍ أفضل من المستهلك. ويتضمن هذا كل تحذيرات السالمة والعناصر ذات الصلة ي ُ رجى قراءة "دليل التعليمات" هذا بالكامل قبل بدء التركيب الفعلي. كما ي ُ رجى إيالء اهتمام خاص لكل تحذيرات السالمة. فغال ب ً ا أثناء التركيب أو اإلصالح، قد .تضع...
Page 63
القسم 1. المتطلبات العامة لجميع استعماالت مجموعات الوصالت الطويلة يجب استخدام الطول المكافئ لتحديد ما إذا كان باإلمكان القيام بتركيب أي مجموعة الوصالت الطويلة. راجع القسم 5 للتعرف على حسابات .الطول المكافئة .بالنسبة ألي نظام سبليت منزلي تم تركيبه بمجموعة الوصالت الطويلة، يجب استخدام وصلة سوائل بحجم 3/8 بوصة من...
Page 64
حمالة دعامة وصلة سوائل جدار مربوطة بوصلة شفط وصلة سوائل جلبة معدنية وصلة شفط Armaflex® مغلقة بـ .1-1 الشكل تركيب شبكة أنابيب التبريد من الوضع العمودي إلى الوضع األفقي .هام - ال يجب أن تلمس وصالت المبرد الجدار وصلة شفط وصلة...
Page 65
إذا كان يتم تعليق مجموعة الوصالت من كمرة أو رافدة، فاستخدم أشرطة معدنية أو أدوات ربط سلكية أدوات ربط سلكية .من النايلون القوي المثبتة بإحكام )(حول وصلة الشفط فقط )8 أقدام (4.2 م كمرات األرضية شريط أو أدوات ربط سلكية أو...
Page 66
.)المركم غير ضروري لمكيفات الهواء (يتم تركيب المراكم على المضخات الحرارية في المصنع .محبس الزيت في الوحدة الداخلية غير مطلوب . غير نزفية في الوحدة الخارجيةTXV وصلة السوائل ذات الملف اللولبي غير مطلوبة إذا تم استخدام القسم 3. الوحدة الخارجية أعلى من الوحدة الداخلية )HP( المضخة...
Page 67
القسم 4. الوحدة الخارجية أدنى من الوحدة الداخلية )HP( المضخة الحرارية )AC( مكيف الهواء الملحق نعم نعم )سخان علبة المرافق (04 واط كحد أدنى نعم نعم بدء التشغيل المتعسر )(راجع الدليل لكل منتج )(راجع الدليل لكل منتج نعم نعم ) (في الداخلTXV وصلة...
Page 68
القسم 5. الحسابات - الطول المكافئ لشبكة األنابيب، حجم األنبوب والمبرد )في إطار استعماالت الوصالت الطويلة، "طول الوصلة المكافئ" هو مجموع مقاطع الطول المستقيم لوصلة الشفط زائد الخسائر (بالطول المكافئ الناجمة عن االنحناءات بزاوية 54 و09 درجة. قم بجمع الطول المستقيم (الخطي) الكلي لشبكة األنابيب مع الطول المكافئ للوصالت المرفقية .واالنحناءات...
Page 70
. المنزلية في المصنع لتناسب 51 قدم ً ا (6.4 م) من مجموعة الوصالتR-410A تعديل كمية المبرد. تم شحن جميع الوحدات الخارجية :)لحساب الكمية األساسية للمبرد اإلضافي (باألونصة اطرح 51 قدم ً ا (6.4 م) من مجموع الطول المستقيم (غير المكافئ) لمجموعة الوصالت الفعلية .أ...
Page 72
مالحظة: تخضع المواصفات وبيانات األداء المدرجة هنا للتغيير دون إشعار !الجودة ت ُ حدث فار ق ً ا يتم تصميم جميع أنظمتنا وتصنيعها وف ق ً ا لمعايير الجودة العالية نفسها بغض النظر عن الحجم أو الفعالية. وقد قمنا بتصميم هذه الوحدات لتقليل أسباب تعطل المنتجات...