Turn off the power supply to the iTM.
• To turn on/off the power supply to the iTM, turn on/off the circuit breaker.
iTM does not have a power on/off switch.
CAUTION
• Do not press the switch with excessive force. Doing so may damage the components and
cause malfunction.
• The iTM contains static-sensitive components.
To prevent electrostatic discharge damage to these components, discharge the static
electricity accumulated in your body before attempting operation.
You can discharge static electricity accumulated in your body by touching a grounded
metal part of the unit (control panel etc.).
<About iTM operation>
When operating on the Standard View screen, touch sound is heard even when an area not
allocated for a button is pressed.
• The iTM screen is designed to sound wherever it is touched. This is normal.
The screen flickers at a regular interval.
• The Standard View screen of the iTM is refreshed every 3 seconds to reflect the air
conditioners current status. The screen flickers each time it is refreshed, but this is normal.
The operation performed by touching the iTM screen takes some time to be reflected on the
screen view.
• Depending on the status of the communication with the connected air conditioners, update of
the screen view may take some time. Please wait a few seconds.
LCD display
• LCD displays are produced using high precision technology but there may be some dots that
never go on, or dots that are permanently on. Furthermore, the LCD display may generate
unevenness due to temperature change and the like. However, these are phenomena inherent
to LCD panels, and are not faults.
An area unit filter sign is ON on the Standard View screen.
• The filter sign does not go off even when the air conditioner filter has been cleaned and the
cleaning sign has been reset using remote controller.
The filter sign on the Standard View screen is designed to go off only when the cleaning signs
for all of the air conditioners in the area are reset.
Check for any air conditioner in the area with the cleaning sign ON apart from the cleaned air
conditioner.