Check that the Output1 tab
Select "At least one input becomes valid" in the Input condition combo box (11).
The step above finishes the setup of the required conditions, "which is either indoor unit "a"
or "b" to be On for 10 minutes".
4. Setting up the target
Touch the Modify button
(13)
is the list of management points and areas that can be registered.
Select Ventilator "c" and touch the Add button to register it as target of the output event in (14).
5. Setting up the output actions
Select the Ventilator "c" registered in
Setup screen appears.
(10)
(10)
is displayed and
(12)
and display the Interlock Program Output Setup screen.
(14)
(15)
(14)
and touch the Action Setup button (15). The Action
User's Manual EM11A015B
intelligent Touch Manager
(12)
(11)
(13)
166