Restrictions for use of the pre-cool/heat function
Please note the following restrictions before using the pre-cool/heat function.
The pre-cool/heat function is designed to operate according to the settings recognized when the
date changes to the day of schedule execution.
Therefore, even if you set the pre-cool/heat function on the very day of schedule execution, the
schedule will operate as a normal schedule, ignoring the pre-cool/heat settings.
To enable the pre-cool/heat function, be sure to make the settings before the day of execution.
• Operation after a setting change
Changes to the schedule settings are enabled at the moment when the date changes.
Even if you change or delete the schedule on the very day of execution, the schedule function
will operate according to the settings recognized when the date changes.
• When changing the date setting of iTM
If the time setting of iTM is changed and the date setting is accordingly changed, pre-cool/heat
already scheduled on the changed date will be ignored and the normal schedule will be
executed.
• When restarting iTM
If iTM is restarted, pre-cool/heat scheduled on the day of restart will be ignored and the normal
schedule will be executed.
• Execution of pre-cool/heat during 0:00 to 2:59
The pre-cool/heat function starts its control 3 hours before the scheduled time after the date
changes to the day of schedule execution.
If you set the pre-cool/heat function to operate during the period from 0:00 to 2:59, the
schedule will operate as a normal schedule, ignoring the pre-cool/heat settings.
• When the daylight saving time starts or ends
Pre-cool/heat may not be executed or may be executed twice depending on the time setting.
• When using an air conditioner without changeover option
Even if you set pre-cool/heat to an air conditioner without changeover option, the setting will
be executed according to the operation mode of an air conditioner with changeover option.
(6)
Stop radio button
Select to stop the target.
(7)
Setback High, Setback Low radio buttons
Select either of the two radio buttons when setting up the Setback function.
These radio buttons are displayed only when the optional Setback function is enabled.
(8)
OK button
Saves the edit and closes the screen.
(9)
Cancel button
Cancels the edit and closes the screen.