Advertisement

4. Remove the wires in the existing terminal blocks
and install in the pressure switch ports as shown
below:
Pressure Switch
Switch Port
Port
Pressure
Pressure
Switch
Port
NO
COM
Air Pressure
Pressure
Air
Air
Pressure
Less than 70 psi (0.5
MPa, 5.0 bar)
Greater than 70 psi
(0.5 MPa, 5.0 bar)
5. Remove unused terminal blocks after connecting
the wires to the pressure switch ports.
6. Connect approximately 1 foot of 5/32" tube from
the pressure switch to the bulkhead on the inside
of the electronics panel.
7. Connect approximately 2 feet of 5/32" tube from
that bulkhead on the electronics panel to the
bulkhead on the side of the unit.
3A8492A
Terminal
Terminal Block
Terminal
Block
Block
3
4
System Stop
System
System
Stop Air
Stop
Air
Air State
State
State
System Stop Air
inactive (system run)
System Stop Air
activated (system
stop)
Wire the
the System
System Stop
Wire
Wire
the
System
The System Stop Digital input provides a means to
signal the HydroShield system to stop. This normally
open contact turns the system off when activated.
If the input is read as CLOSED, it stops system
operation and puts the system into Off mode. If the
input is read as OPEN, the system operates normally.
Prepare the electrical controls
for service. Follow the steps in
Prepare the Electrical Controls for Service, page
The System Stop Digital input uses an optocoupler
to protect the HydroShield controls from outside
voltages.
Optocoupler Port
Port
Optocoupler
Optocoupler
Port
13+
14
A1+
A2–
Apply the 24 VDC signal to A1+ and GND to A2–.
Only one A2– port needs to be connected to GND, as
the two ports labeled A2– are connected internally.
Function
Function
Function
System Stop: Digital
activated (system stop)
System Stop: Digital
inactive (system run)
Installation
Stop Digital
Digital Input
Input
Stop
Digital
Input
Connect to to to
Connect
Connect
Control module
External device
or PLC
A1+
A1+ (relative
A1+
(relative
(relative to to to A2–)
A2–)
A2–)
24 VDC
Less than 13.5 VDC
106.
25