Table 13
13 Color
Color Change
Change Events
Table
Table
13
Color
Change
Type
Code
Code
Code
Type
Type
WSF0
Advisory
WSCX
Advisory
WSC0
Advisory
WS##
Record
WSFX
Alarm
L7F0
Advisory
DE00
Alarm
3A8492A
Events
Events
Name
Name
Name
Rejected Inlet Change User is unable to
Invalid Presets
Invalid Preset
Selected
Invalid Preset ##
Invalid Inlet Valve
Flush Fluid In Pump
Purge Timeout
Description
Description
Description
change color/inlet
valve during operation
and is notified via an
advisory.
User decreases the
number of color
change valves,
creating invalid
presets. In this error
code, the last digit X
means system.
User has invalid
presets due to
changing the number
of color change valves
and selects an invalid
preset.
User has invalid
presets due to
changing the number
of color change
valves and selects
and invalid preset.
Records in which
preset is invalid, ## is
the Preset number.
User decreased the
number of color
change valves during
system operation,
resulting in an invalid
selected inlet valve.
In this error code, X
means system.
Flush Fluid is still
in the pump when
entering Spray Mode.
Pump volume did not
change before the
timeout expired.
Error Codes
Solution
Solution
Solution
Changing of Color value is not
allowed in Spray mode. Change
to Off, Standby or Prime to change
colors.
Confirm that the number of color
valves is correct, and then correct
presets with invalid colors
See
System Screen, page 66
Presets, page
52.
The color setting for the current
preset is not correct. Confirm that
the number of colors valves for the
system matches the system setting,
confirm that the current preset has
the correct color setting.
See
System Screen, page 66
Presets, page
52.
Confirm that the number of color
valves is correct, and then correct
the presets that contain invalid
colors.
See
System Screen, page 66
Presets, page
52.
Confirm that the number of color
valves is correct, and then correct
the presets that contain invalid
colors.
See
System Screen, page 66
Presets, page
52.
Empty out the flush fluid from the
pump then go back into Spray
Mode.
Determine why the pump volume
was not changing and restart the
purge sequence.
See
Purge Screens 1–5, page
and
and
and
and
53.
89