Introduction

1.5 Frequently required parameters

1.5
Frequently required parameters
Parameters that in many cases help
Table 1- 2
How to switch to commissioning mode or restore the factory setting
Parameter
Description
P0010
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
3: Perform motor commissioning
5: Technological applications and units
15: Define number of data records
30: Factory setting - initiate restore factory settings
Table 1- 3
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
Table 1- 4
This is how you select the command source of the control signals (ON/OFF, reversing) of the inverter
Parameter
Description
P0700
2: Digital inputs (P0701 ... P0709); factory setting for inverters without PROFIBUS interface
6: Fieldbus (P2050 ... P02091), factory setting for inverters with PROFIBUS interface
Table 1- 5
This is how you select the setpoint source for the speed
Parameter
Description
P1000
0: No main setpoint
1: Motorized potentiometer
2: Analog setpoint; factory setting for inverters without PROFIBUS interface
3: Fixed speed setpoint
6: Fieldbus; factory setting for inverters with PROFIBUS interface
7: Analog setpoint 2
Table 1- 6
This is how you parameterize the up and down ramps
Parameter
Description
P1080
Minimum speed
0.00 [rpm] factory setting
P1082
Maximum speed
1500.000 [rpm] factory setting
P1120
Rampup time
10.00 [s]
P1121
Rampdown time
10.00 [s]
18
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA