List Of Warnings - Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

9.3

List of warnings

Table 9- 7
The most important warnings
Number
Cause
A01028
Configuration error
A01590
Motor maintenance interval
lapsed
A01900
PROFIBUS: Configuration
telegram faulty
A01920
PROFIBUS: Cyclic connection
interrupt
A03520
Temperature sensor fault
A05000
Power Module overtemperature Check the following:
A05001
A07012
I2t Motor Module
overtemperature
A07015
Motor temperature sensor
alarm
A07321
Automatic restart active
A07850
External alarm 1 ... 3
A07851
A07852
A07903
Motor speed deviation
A07910
Motor overtemperature
A07927
DC braking active
A07980
Rotary measurement activated
A07981
No enabling for rotary
measurement
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Remedy
Explanation: Parameterization on the memory card has been created with a
different type of module (order number, MLFB)
Check the module parameters and recommission if necessary.
Carry out maintenance and reset the maintenance interval (p0651).
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty configuration telegram.
Check the bus configuration on the master and slave side.
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
with cyclic operation.
Check that the sensor is connected correctly.
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is
automatically switched back on.
The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for the
external alarm 1... 3.
Remedy: Rectify the cause of this alarm.
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
Not required
Not required
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Alarms, faults and system messages
9.3 List of warnings
249