Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 255

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Extended settings for faults
Table 9- 10
Parameter
You can change the fault response of the motor for up to 20 different fault codes:
p2100
p2101
You can change the acknowledgement type for up to 20 different fault codes:
p2126
p2127
You can change up to 20 different faults into an alarm or suppress faults:
p2118
p2119
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Advanced settings
Description
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
Setting, fault response
Setting the fault response for the selected fault
Setting the fault number for the acknowledgement mode
Selecting the faults for which the acknowledgement type should be changed
Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
Setting the message number for the message type
Selecting the message for which the message type should be selected
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
Alarms, faults and system messages
9.4 Faults
255