1.4 Frequently required parameters

1.4
Frequently required parameters
Parameters that in many cases help
Table 1- 1
How to switch to commissioning mode or restore the factory setting
Parameter
Description
p0010
Commissioning parameters
0: Ready (factory setting)
1: Carry out basic commissioning
3: Perform motor commissioning
5: Technological applications and units
15: Define number of data records
30: Factory setting - initiate restore factory settings
Table 1- 2
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
Table 1- 3
How to select the command and setpoint sources for the inverter
Parameter
Description
p0015
Additional information is available in the section Selecting the interface assignments (Page 48).
Table 1- 4
This is how you parameterize the up and down ramps
Parameter
Description
p1080
Minimum speed
0.00 [rpm] factory setting
p1082
Maximum speed
1500.000 [rpm] factory setting
p1120
Rampup time
10.00 [s]
p1121
Rampdown time
10.00 [s]