Telegram Monitoring - Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Connection to a fieldbus
6.4 Communication via RS485
The number of PZD words in a USS telegram is defined by parameter p2022. The first two
words are:
● Control 1 (STW1, r0054) and main setpoint (HSW)
● Status word 1 (ZSW1, r0052) and main actual value (HIW)
If P2022 is greater than or the same as 4, the additional control word (STW2, r0055) is
transferred as the fourth PZD word (default setting).
You define the sources of the PZD using parameter p2051.
For further information, please refer to the Parameter Manual.
6.4.2.8

Telegram monitoring

You require the telegram runtimes in order to set the telegram monitoring. The character
runtime is the basis of the telegram runtime:
Table 6- 26
Baud rate in bit/s
9600
19200
38400
115200
The telegram runtime is longer than just purely adding all of the character runtimes
(=residual runtime). The character delay time between the individual characters of the
telegram also has to be taken into account.
Figure 6-17
The total telegram runtime is always less than 150% of the pure residual runtime.
Before each request telegram, the master must maintain the start delay. The start delay
must be > 2 * character runtime.
142
Character runtime
Transmission time per bit
104.170 µs
52.084 µs
26.042 µs
5.340 µs
Residual runtime
(compressed telegram)
Telegram runtime as the sum of the residual runtime and character delay times
Character run time (= 11 bits)
1.146 ms
0.573 ms
0.286 ms
0.059 ms
50% of compressed
telegram residual runtime
: : :
: : :
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA