Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 102

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Configuring the terminal block
5.5 Analog outputs
Table 5- 12
Parameter
p07xx[0]: AO 0
p07xx[1]: AO 1
p0773[x]
p0775[x]
p0782[x]
102
Additional analog output settings
Description
Analog outputs smoothing time constant
Smoothing time constant of 1st order low-pass filter for the analog outputs
Activate absolute-value generation
0: No absolute-value generation (factory setting)
1. The absolute value of the analog output is used.
If the original value was negative, the corresponding bit is set in the status word of
the analog input (r0785).
Analog outputs signal source for inverting
Signal source to invert the analog output signals
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA