Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 234

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Functions
7.11 Switchover between different settings
Figure 7-31
Use parameter P0180 to define the number of command data sets (2, 3 or 4).
Table 7- 46
Parameter
P0010 = 15
P0180
P0010 = 0
The drive data sets are switched over using parameters P0820 and P0821. Parameters
P0820 and P0821 are interlinked to control commands, e.g. the digital inputs of the inverter,
using BICO technology.
234
DDS switchover in the inverter
Selecting the number of command data sets
Description
Drive commissioning: Data sets
Number of drive data sets (factory setting: 1)
P0180 = 1, 2, 3 or 4
Drive commissioning: Ready
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA