Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 145

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

The setting using DIP switches is described in Setting the bus address via DIP switch
(Page 104).
CAUTION
A bus address that has been changed is only effective after switching-off and switching-on
again. It is particularly important that any external 24 V supply is switched off.
Additional communication settings
Table 6- 28
Parameter
p0700 = 6
p1000 = 6
p2030 = 2
p2020
p2024
p2029
p2040
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Parameters for setting communication via Modbus
Description
Select the command source
6: Via fieldbus
Select the setpoint source
6: Via fieldbus
Fieldbus telegram selection
2: Modbus
Fieldbus baud rate
Baud rates from 4800 bit/s to 19200 bit/s can be set for communication, factory setting =
19200 bit/s.
Modbus timing (see Section "Baud rates and mapping tables (Page 147)")
Index 0: Maximum slave telegram processing time:
The time after which the slave must have sent a response to the master.
Index 1: Character delay time:
Character delay time: Maximum permissible delay time between the individual
characters in the Modbus frame. (Modbus standard processing time for 1.5 bytes).
Index2: Inter-telegram delay:
Maximum permissible delay time between Modbus telegrams. (Modbus standard
processing time for 3.5 bytes).
Fieldbus fault statistics
Displays receive faults on the fieldbus interface
Process data monitoring time
Determines the time after which an alarm is generated if no process data are
transferred.
Note: This time must be adapted depending on the number of slaves and the baud rate
set for the bus (factory setting = 100 ms).
Connection to a fieldbus
6.4 Communication via RS485
145

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu240e-2Sinamics g120 cu240b-2 dpSinamics g120 cu240e-2 dpSinamics g120 cu240e-2 fSinamics g120 cu240e-2 dp-f

Table of Contents