Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 99

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Example: Setting the analog inputs to 4 - 20 mA
Terminal No.
and
Significance
3
4
10
11
When p0756 is changed to value 3, the parameters of the scaling characteristic are automatically
overwritten with the following values:
p0757 = 4.0, p0758 = 0.0, p0759 = 20, p0760 = 100
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Parameter
AI 0+
p0756[0] = 3
AI 0-
AI 1+
p0756[1] = 3
AI 1-
p0761[0] = 4.0
p0761[1] = 4.0
Description
Analog input type 0
2: Unipolar current input (0 mA
...20 mA)
Analog input type 1
2: Unipolar current input (0 mA
...20 mA)
Wire breakage monitoring response threshold
Configuring the terminal block
5.4 Analog inputs
Setting DIP switch to current
input ("I"):
99