Frequently Required Parameters - Siemens SINAMICS G110D Operating Instructions Manual

Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

Introduction
2.2 Adapting the Inverter to the application
2.2.4

Frequently required parameters

Parameters that in many cases help
Table 2- 1
This is how you filter the parameter list to keep the number of displayed parameters to a minimum
Parameter
Description
P0003 =
User access level
1: Standard: Allows access to the most frequently used parameters (factory setting)
2: Extended: Extended access, e.g. to inverter I/O functions
3: Expert: To be used by experts
P0004 =
Parameter filter
0: All the parameters are displayed (factory setting).
2: Inverter
3: Motor - data of the motor and output filter are displayed
Table 2- 2
How to switch to commissioning mode or restore the factory setting
Parameter
Description
P0010 =
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
30: Factory setting - initiate restore factory settings
Table 2- 3
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
Table 2- 4
This is how you reset the parameters to the factory setting
Parameter
Description
P0010 = 30
30: Factory setting - initiate restore factory settings
P0970 = 1
1: Resetting - restoring all parameters to the factory setting
Table 2- 5
This is how you select the command source of the control signals (ON/OFF, reversing) of the inverter
Parameter
Description
P0700 =
0: Factory default setting
2: Digital inputs
4: USS on RS 232
6: Fieldbus ; default setting
16
Operating Instructions, 2009-05-15, A5E02385577A AB
SINAMICS G110D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents