Commissioning
4.5 Commissioning with STARTER
Carry-out basic commissioning
The configuration wizard guides you step by step through the commissioning procedure.
After the basic commissioning, you can change all of the settings and make detailed
changes.
● In the start dialog box of the basic commissioning, select the control mode of the motor. If
● With "Continue" you can go to the next dialog boxes where you must make the
● In the "Drive functions" dialog, we recommend the setting "Identify motor data at standstill
● If the motor cannot rotate freely, e.g. where travel is mechanically limited, select the
82
you are not certain which control mode you require for your application, then initially
select V/f control. Help on how to select the control mode is provided in Chapter Motor
control (Page 168).
Figure 4-8
Basic commissioning with V/f control
appropriate settings for your particular application.
and with the motor rotating".
setting "Identify motor data at standstill".
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA