Siemens SINAMICS G120 CU240B-2 Operating Instructions Manual page 61

With the control units
Hide thumbs Also See for SINAMICS G120 CU240B-2:
Table of Contents

Advertisement

Table 4- 1
Command and setpoint sources
Parameter
P0700 = 2 or 6
P1000 = 2 or 6
Table 4- 2
Factory settings of additional important parameters
Parameter
Factory setting
P0010
0
P0100
0
P0300
1
P0304
400
P0305
depends on the
Power Module
P0307
depends on the
Power Module
P0308
0
P0310
50
P0311
1395
P0335
0
P0625
20
P0640
200
P0970
0
P1080
0
P1082
50
P1120
10
P1121
10
P1300
0
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Description
Select the command source
2: Digital inputs (P0701 ... P0709) (factory setting for CUs without PROFIBUS interface)
6: Fieldbus (P2050 ... P2091), (factory setting for CUs with PROFIBUS DP interface)
Select the setpoint source
2: Analog setpoint (factory setting for CUs without PROFIBUS DP interface)
6: Fieldbus (factory setting for CUs with PROFIBUS DP interface)
Meaning of the factory
setting
Ready to be entered
Europe [50 Hz]
Induction motor
[V]
[A]
[kW/hp]
[cos phi]
[Hz]
[rpm]
Non-ventilated: Shaft-
mounted fan in the motor
[°C]
[A]
Locked
[rpm]
[rpm]
[s]
[s]
V/f control with linear
characteristic
4.3 Commissioning with factory settings
Name of the parameter and comments
Drive, commissioning parameter filter
IEC/NEMA motor standard
IEC, Europe
NEMA, North America
Note: This parameter cannot cannot be changed in FW4.3.
Motor type selection (induction motors / synchronous
motor)
Rated motor voltage (in accordance with the rating plate in
V)
Rated motor current (in accordance with the rating plate in
A)
Rated motor power (in accordance with the rating plate in
kW/hp)
Rated motor power factor (in accordance with the rating
plate in cos 'phi'). If P0100=1, 2, then P0308 has no
significance.
Rated motor frequency (in accordance with the rating plate
in Hz)
Rated motor speed (in accordance with the rating plate in
rpm)
Motor cooling type (specify the motor cooling system)
Motor ambient temperature
Current limit (of the motor)
Reset drive parameters (restore to the factory settings)
Minimum speed
Maximum speed
Ramp-function generator, ramp-up time
Ramp-function generator, ramp-down time
Open-loop/closed-loop control operating mode
Commissioning
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu240e-2Sinamics g120 cu240b-2 dpSinamics g120 cu240e-2 dpSinamics g120 cu240e-2 fSinamics g120 cu240e-2 dp-f

Table of Contents