Motorized potentiometer parameters
Table 7- 4
Parameter
P1000 = 1
P1047
P1048
P1040
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Figure 7-3
Function chart of motorized potentiometer
Basic setup of motorized potentiometer
Description
Select speed setpoint
1: Motorized potentiometer
MOP ramp-up time (factory setting 10 s)
MOP ramp-down time (factory setting 10 s)
Start value of MOP (factory setting 0 rpm)
Determines the start value [rpm] that becomes effective when the motor is switched
on
Functions
7.4 Setpoint sources
161