Point Assignments; P## Alarm Verify; P## Resettable; Point Number - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 4.0

P## Alarm Verify

Default:
Refer to the program record sheet
Selection:
Yes or No
Yes
Enable alarm verification on this point.
Alarm verification points must be
programmed as resettable.
No
Disable alarm verification on this
point.
Use this option only with Fire points to designate them
for alarm verification.
When an Alarm Verification point enters into alarm,
the control panel removes power to all Resettable
points for the duration programmed in
Time
in Section 2.9 Area Parameters on page 32. If the
point (or another Resettable point in the area) is still
faulted, or returns to a faulted state within 60 seconds
after the initial verification time reset, an alarm is
generated.
During a Fire Walk Test the reset time is 5
seconds. The time programmed in A#
Verify Time is ignored. Use the Cross point
function for Fire points.

P## Resettable

Default:
Refer to the program record sheet
Selection:
Yes or No
Yes
This point is reset by the Reset Sensor?
function and during the alarm
verification sequence.
No
This point is not resettable.
Use this option if this is a Powered point that requires
interruption of power to reset a latched alarm
condition. The Resettable point option is typically used
with smoke detectors and glass break detectors.
When initiated (either through a Fire Walk Test or the
keypad's Reset Sensor? function) or when the remote
programming software (RPS) interrupts power to the
device for 5 seconds, a Sensor Reset report is sent to
the central station receiver.
When a sensor reset occurs, the control
panel does not accept alarms from any
points with P## Resettable programmed
as Yes. During the 5-second reset time,
alarms from these points are ignored.
Do not mix fire and intrusion devices on the
same powered loop.
Bosch Security Systems | 5/05 | F001U003636B
RADXPNTS
4.3
These entries assign point indexes to Points 1 to 127,
129 to 247 for the D9412GV2 and Points 1 to 75 for
the D7412GV2, and assign the points to the areas.
Also included in this section are parameters used to set
the point's debounce count, BFSK/Relay (for use when
transmitting in BFSK or assigning relays to follow
alarms for a group of points), and custom keypad and
report text for each point.

Point Number

Default:
Selection:
Enter the point number you are programming. When
A# Verify
transmitting in Modem IIIa
number is reported to the D6500 or D6600. When
transmitting in BFSK, you must assign a zone number
in BFSK/Relay.

Point Assignments

1
1 to 127, 129 to 247
2
, the three-digit point
Point number 128 is reserved for
supervising Zonex 1.
Point number 248 is reserved for
supervising Zonex 2.
EN | 94