P## Buzz On Fault

Default:
Blank
Selection:
Blank, 1 to 3
Selection
Operation for Controlled Points
(Point Types 1, 2, and 3)
Blank
The point buzzes at the keypad only if it enters
into the trouble condition indicated in the
Point Response
1
The point generates a Buzz Until Restore at the
keypad for any fault condition while the point
is disarmed. The buzz continues until the point
restores and the user acknowledges the condition
using a pass code or COMMAND 4. The point
must be normal before the user can silence the
buzz.
2
The point buzzes at the keypad for any fault
condition when the point is disarmed. The
user can silence the buzz before the point returns
to normal.
3
The point buzzes at the keypad for any fault
condition when the area is disarmed. The user
cannot silence this buzz, but it silences
automatically when the point is restored. If the
fault condition results in a trouble response, the
keypad continues to buzz even after the user
acknowledges the condition if the fault is still
present.
Points bypassed (by the user, Sked,
Swinger Bypass, or RPS) do not generate
a Buzz On Fault condition at the keypad.
The buzz does not automatically stop when
the point is restored when using Option 1
or 2. The user must acknowledge the buzz
before the buzz stops. However, when
using Option 3, the buzz stops
automatically when the point restores to
normal without user intervention.
Bosch Security Systems | 5/05 | F001U003636B
RADXPNTS
.
Operation for 24-hour Points
(Point Type 0)
Same as as operation for controlled points
P##
The point generates a Buzz Until Restore at
the keypad for any fault condition
regardless of the armed state. The buzz
continues until the point restores and the user
acknowledges the condition using a pass code
or COMMAND 4. The point must be normal
before the user can silence the buzz.
The point buzzes at the keypad for any fault
condition regardless of the armed state.
The point does not need to be normal before
the user can silence the buzz.
The point buzzes at the keypad for any fault
condition regardless of the armed state.
The user cannot silence this buzz, but it
silences automatically when the point is
restored. If the fault condition results in a
trouble response, the keypad continues to
buzz even after the user acknowledges the
condition if the fault is still present.

P## Watch Point

Default:
Refer to the program record sheet
Selection:
Yes or No
Yes
Activates Watch Mode responses if the
point is faulted while the control panel
is in Watch Mode.
No
Does not activate Watch Mode
responses for this point.
Use this option to allow a Controlled point to generate
a watch tone while the area is disarmed and not
faulted to a trouble or alarm condition.
EN | 89