Printer Parameters; Printer Address; P## Supervised; P## Scope - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 2.0
2.6

Printer Parameters

Up to three D9131A Parallel Printer Interface Modules
can be connected to the D9412GV2's (one printer for
the D7412GV2's) SDI bus. Each printer is identified
by an address of 17, 18, or 19. Options are available
for Routing Reports and area assignments.

Printer Address

Default:
17
Selection:
17, 18, or 19 (only 17 is available for
the D7412GV2)
Enter the printer address you are programming.
P## Area Assign
Default:
1
Selection:
1 to 8
Assign an area to the printer programmed in
Address
.

P## Supervised

Default:
No
Selection:
Yes or No
Yes
Only one printer can be installed for
P## SDI
this
No
More than one unsupervised printer
can be installed using this
address and the same address DIP
switch setting.
Supervise this SDI address. Generate Trouble SDI ##
Reports and local trouble annunciation if a problem
occurs with this printer or the SDI bus.
Unsupervised printers sharing the same
address setting print the same text.
Trouble SDI ## Reports are always
reported as Area 1, Account 1 Events
regardless of where the SDI device is
assigned.
When P## Supervised is set to Yes and
all Printer Event Groups (such as P## Fire
Events, P## Burglar Event, or P## Usr
Chng Evt) are set to No, the control panel
does not generate Trouble SDI ## Reports
for the printer if the D9131A becomes
disconnected.
Bosch Security Systems | 5/05 | F001U003636B
Printer
address.
P## SDI
GV2MAIN

P## Scope

Default:
No Printer
Selection:
No Printer, Area, Account, Panel
Wide, Custom
Panel
Printer prints all designated events that
Wide
occur panel-wide. A panel-wide printer
can cross account boundaries.
Account
Printer prints all designated events that
occur within any area with the same
account number in which this printer
is assigned.
Area
Printer prints all designated events that
occur in the area to which this printer
is assigned.
Custom
Printer prints all events occurring in
areas programmed Yes for this prompt
regardless of any boundary restrictions.
No Printer
No printer installed at this address. If a
printer is connected, data does not
print.
Press the [SPACE] bar to scroll through the selections.
Press [ENTER] when the correct selection appears in
the display.
The following prompts are visible only
when you program P## Scope to Custom.

P## A1 [through A8] in Scope

Default:
No
Selection:
Yes or No
Yes
Include Area # Events in the scope of
this printer.
No
Does not include Area # Events in the
scope of this printer.
P## Scope
Only available if
This program item determines if events occurring in an
area print at this printer.
Refer to the report tables in Section 2.3
Routing on page 13 to identify the events
that print. Events programmed as No in
Routing still print at the local printer.
Individual events within the report group
cannot be suppressed for events printed at
the local printer.
EN | 27
is programmed Custom.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: