D9412GV3/D7412GV3/D7212GV3
6

Setting Up Points and Outputs

6.1

Using the Relay Option Within Point Assignments

Relay Programming allows any one point or several points to latch a single relay through
software when the selected point generates an alarm. Relays are number 1 through 8 and are
programmed by entering the number of the relay (1 - 8) in the Relay column in Point
Assignments. This relay latches on a generated alarm and resets after acknowledging and then
clearing the alarm from memory.
Relay
1
2
3
4
5
6
7
8
1
For the D7412GV3 and D7212GV3, connect to Terminal 28 for data (Zonex 1 Out)
2
For the D9412GV3, connect to Terminal 26 for data (Zonex 2 Out)
Table 6.1 Actual Relays Latched by Control Panel Type
Switch Number
1
2
3
4
Table 6.2 D8129 Switch Settings for All Control Panel Types
NOTICE!
Programmers must be aware of the following considerations:
Bosch Security Systems, Inc.
D8129 Actual Relay Number
D7412GV3/D7212GV3
9
10
11
12
13
14
15
16
Setting
ON
OFF
ON
ON
Do not use relays designated within Point Assignments for multiple functions. For
example, Relays 73 through 80 on the D9412GV3 should not be used for relay-follow-
point or area-wide or panel-wide relays.
Relays should not be selected to follow points programmed as Invisible Points.
Quick Reference Guide
Setting Up Points and Outputs | en
1
2
D9412GV3
73
74
75
76
77
78
79
80
.
13
.
F01U170805 | 01 | 2010.11