D9412GV2/D7412GV2 | Program Entry Guide | 4.0
P ## Type
Description
Selection
2
Interior: Interior points are armed only by master arming the area. They are not armed when
using Perimeter Arming functions. These points are typically used to monitor interior detection
devices such as interior doors, motion detectors, photoelectric beams, and carpet mats.
Instant Interior Points: Interior points are usually programmed for an instant alarm (refer to
Section 4.2 Point Responses on page 85). Points programmed for instant alarms generate alarms
immediately, even during entry or exit delay.
Delayed Interior Points: Interior points can be programmed for a delayed point response. A
delayed response means that if the point is faulted while the area is armed, it activates entry
delay. It does not generate an alarm until entry delay expires.
When an Interior point is programmed for entry delay, entry delay time is always provided. If
the area is in entry delay when a fault occurs for the Interior point, the control panel compares
the remaining entry delay time to the time programmed for the Interior point. If the Interior
point's entry delay time is less than the remaining time, it shortens the entry delay time.
Delayed points can also activate an entry tone at the keypad (refer to the
prompt in Section 4.2 Point Responses on page 85).
In some cases, you might need to create an Interior point that causes an instant alarm if the entry
delay is not started first. Use Interior Follower to create this type of protection.
Interior Follower: Interior Follower points are armed only by master arming the area. They are
3
not armed when using Perimeter-Arming functions.
An Interior Follower point does not create an alarm if it has a fault while the area is in entry
delay. An Interior Follower does not change the amount of remaining entry delay time.
If no entry delay is in effect when a fault occurs for the Interior Follower, it creates an instant
alarm.
You must program a delayed Point Response (4, 5, 6, 7, or 8) for an Interior Follower point. The
control panel ignores the entry in
Note:
Increasing the debounce count for Interior Follower points might be necessary to prevent
Interior Follower points from entering into alarm before the control panel recognizes that a
Perimeter Delay point was faulted. Program the Interior Follower's debounce for one
number higher than the debounce count on Perimeter delay
Bosch Security Systems | 5/05 | F001U003636B
RADXPNTS
P## Entry Delay
for an Interior Follower point.
EN | 82