D9412GV2/D7412GV2 | Program Entry Guide | 4.0

4.0 RADXPNTS

4.1

Point Index

Use this programming module to construct personality
types for points used in the system. The Index
numbers are used in Point Assignments. Each unique
point index number determines the control panel's
responses to specific conditions occurring on the
Protective points.

P## Type

Default:
Refer to the program record sheet
Selection:
0 to 9
P ## Type
Description
0
24-hour: A 24-hour point is not turned on and off from a keypad. 24-hour points are armed all
the time, and can be used for fire protection (refer to the
Point Responses on page 85), panic, medical, and police alerts.
24-hour points can be programmed as bypassable. Consider the application carefully before
using the bypassable option. Program bypassable 24-hour points to Buzz on Fault.
When a 24-hour point is bypassed, send the report as it occurs. If the area contains all 24-hour
points, the area is never armed or disarmed. A Deferred Bypass Report is not sent.
24-hour protection for fire doors, roof hatches, and so on. Instead of programming this type of
protection as a 24-hour point, consider using a Perimeter point type with a Point Response of 9
to E. 24-hour points do not show faults when an arming function is entered, but Perimeter points
do. When programming this type of protection, consider also using the Buzz on Fault and Local
While Disarmed options.
1
Perimeter: Perimeter points are armed with all arming functions. Points programmed as
perimeter can also be armed as a group (using Perimeter-Arming functions) separately from
points programmed as interior. This lets the user partially arm the system to establish Perimeter
protection while occupying the interior of the protected premises.
Perimeter points can be programmed to activate entry delay time. If the point activates entry
delay, it can also activate an entry tone.
When a Perimeter point is programmed for entry delay, entry delay time is always provided. If
the area is in entry delay when a second Perimeter point is faulted, the control panel compares
the remaining entry delay time to the time programmed for the second Perimeter point. If the
second Perimeter point's entry delay time is less than the remaining time, it shortens the entry
delay time.
Perimeter points programmed for an instant point response, generate an alarm immediately
when faulted, even during entry or exit delay.
Bosch Security Systems | 5/05 | F001U003636B
RADXPNTS
The NEW RECORD program contains default entries
and descriptions that match RPS defaults for point
indexes. Refer to the D9412GV2/D7412GV2 Program
Record Sheet (P/N: F01U003635) for defaults.

Point Index

Default:
1
Selection:
1 to 31
The number of the point personality you are
programming. You can define up to 31 individual
personalities.
P ## Fire Point
EN | 81
prompt in Section 4.2