P## Audible After 2 Failures; P## Invisible Pt - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 4.0
If the point restores and the fire alarm is not
silenced from the keypad, the fire alarm
output continues until Fire Bell time expires.
If the point does not restore, the fire alarm
output continues even after bell time
expires.
Use this option for fire applications to meet
the requirement that audible alarms cannot
be silenced until the fault condition clears
or the Fire Bell time expires.

P## Audible After 2 Failures

Default:
No
Selection
Yes or No
:
Yes
A# Burg Alarm
two failed attempts.
No
P## Silent points do not cause the
Burg Alarm
the report does not get to the central
station receiver.
When set to Yes, if the report fails to reach the central
station after two attempts, a silent alarm rings the
Burg Alarm
bell. A silent alarm is generated when a
P## Silent
point with
armed.
When a point programmed for P## Silent
Bell is faulted, the timer for the A# Burg
Time starts, even though the bell is not yet
ringing. As much as three minutes can
elapse before the second attempt fails.
Ensure that A# Burg Time is programmed
to provide the amount of bell time you
need, minus the additional three minutes
that might elapse before the bell actually
begins to ring.
Bosch Security Systems | 5/05 | F001U003636B
relay activates after
relay to activate even if
set to Yes is faulted while
RADXPNTS

P## Invisible Pt

Default:
Selection:
Yes
No
Use this option to determine whether the point
appears in the keypad display upon an alarm
condition. For LED keypads, the LED does not
illuminate upon an alarm condition. Point text appears
and annunciation is made for Invisible points
programmed for a trouble condition in point response.
To prevent the keypad alarm tone and the
A# Burg Alarm bell from sounding,
program P## Silence Bell as Yes.
A#
If a user enters a valid pass code while a
bell is ringing for an invisible alarm, the
keypad shows ALARM SILENCED.
A##
Refer to the program record sheet
Yes or No
Keypads do not display alarm activity
from this point.
Activity from this point is visible at
the keypads.
EN | 88