D9412GV2/D7412GV2 | Program Entry Guide | 2.0
Programming Tips
1. Burg Time needs a programmed bell period. This
relay activates according to the bell pattern and
remains active until the bell time expires or a valid
pass code is entered.
2. Programming 64 in the Silent Alarm Relay for
Area 8 causes the Area Armed or Perimeter
Armed Relay (refer to Programming Tip 5) to
activate at the beginning of the exit delay time.
3. Programming a non-zero value in the Silent Alarm
Relay for Area 5 enables Ground Fault Detect on
the D9412GV2 or D7412GV2 Control Panel.
Refer to Ground Fault Detect in the
D9412GV2/D7412GV2 Operation and Installation
Guide (P/N: F01U003641).
Fire Trouble Resound
4. When enabled,
the Fire Trouble condition at 12:00 PM or 12:00
AM if the Fire Trouble condition still exists. It
does not, however, retransmit the Fire Trouble
condition. The Fire Trouble Event is only sent, if
programmed to do so, when it occurs.
To disable the Fire Trouble Resound feature,
program a 0 in the Silent Alarm Relay entry
for Area 6.
To enable the Fire Trouble Resound feature at
12:00 PM, program a 61 in the Silent Alarm
Relay entry for Area 6.
To enable the Fire Trouble Resound feature at
12:00 AM, program a 62 in the Silent Alarm
Relay entry for Area 6.
5. Perimeter Armed Relay, when enabled, turns the
Fail to Close Relay function into a Perimeter
Armed Relay function.
To change the Fail to Close Relay into a Perimeter
Armed Relay function, set A7 Silent to 63. Set
Fail to Close Relay
Armed. Refer to Programming Tip 2 for additional
information.
Programming a value other than 0, 61, or
62 enables the Fire Trouble Resound
feature at 12:00 AM.
Bosch Security Systems | 5/05 | F001U003636B
resounds
to the area to be Perimeter
GV2MAIN

2.13.2 Panel-Wide Relays

The following eleven relay options activate when they
occur anywhere in the control panel. They are not
restricted by area boundaries.

AC Failure

Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when the control panel responds to an AC
power failure as programmed in
Section 2.5 Power Supervision on page 25. This relay
automatically resets when AC power restores.
Use this relay to create audible
annunciation. Enable the keypad's trouble
sounders for all applications except
commercial fire systems.

Battery Trouble

Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing condition.
This relay automatically resets when battery power
restores.
Use this relay to create audible
annunciation. Enable the keypad's trouble
sounders for all applications except
commercial fire systems.
A#

Phone Fail

Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for
D7412GV2), A, B, or C
Activates when a telephone line failure occurs. A time
must be entered in Ph Supv Time (refer to Section 2.2
Phone Parameters on page 10) for this relay to activate.
This relay resets automatically when restoral of the
phone line(s) occurs.
EN | 74