D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN

AC/Battery Buzz

Default:
No
Selection:
Yes or No
Yes
Initiates panel-wide trouble tone at all
command centers.
No
Does not initiate panel-wide trouble
tone at command centers
Initiate a panel-wide trouble tone at command
centers when AC fails or battery is low or missing.
This program item does not prevent the SERVC AC
FAIL or SERVC BATT LOW displays.
0101
To comply with NFPA standards and UL
0101
864 requirements for commercial fire
0101
systems, program this item as Yes.
De-selecting individual command centers
for panel-wide trouble tones: Panel-wide
trouble tones for programming the CC
Trouble Tone in the command center
parameters to No can turn off individual
command centers [based on their CC# (1
to 8)].

Bat Fail/Res Rpt

Default:
Yes
Selection:
Yes or No
Yes
Battery Failure and Restoral Reports are sent
to the central station. They are routed to the
telephone number programmed for
Power/Phone Events.
Modem
Missing or
Reports
shorted
Discharged
below 12.1 VDC
BFSK
Missing, shorted
Reports
low battery
No
Battery Failure and Restoral Reports are NOT
sent to the central station.
0101
To comply with NFPA standards and UL
0101
0101
864 requirements for commercial fire
systems, program this item as Yes.
Bosch Security Systems | 10/03 | 47775E
2.6
Up to three D9131A Parallel Printer Interface
Modules can be connected to the D9412G's (one
printer for the D7412G's) SDI bus. Each printer is
identified by an address of 17, 18, or 19. Options are
available for Routing Reports and area assignments.

Printer Address

Default:
Selection:
Enter the printer address you are programming.
P## Area Assign
Default:
Selection:
Assign an area to the printer programmed in
Address

P## Supervised

Default:
Selection:
Yes
No
Supervise this SDI address and generate Trouble
SDI ## Reports and local trouble annunciation if a
problem occurs with this printer or the SDI bus.
BATTERY
MISSING
BATTERY LOW
TROUBLE
ZONE 9

Printer Parameters

17
17, 18, or 19 (only 17 is available for
the D7412G)
1
1 to 8
.
No
Yes or No
Only one printer can be installed for
P## SDI
this
address.
More than one unsupervised printer
can be installed using this
address using the same address DIP
switch setting.
Unsupervised printers sharing the same
address setting print the same text.
Trouble SDI ## Reports are always
reported as Area 1, Account 1 Events
regardless of where the SDI device is
assigned.
EN | 29