4.7 Program Analog Inputs

To program Analog Inputs, select PROGRAM ANALOG INPUTS on the Main Program Menu. Select an
AI to program.
Prompt
INPUT ALGORITHM
Standard algorithm prompts
Table 4-6 describes all the prompts associated with the standard algorithm. These are the default prompts
for analog input programming. See Table 4-2 for additional prompts.
Prompt
INPUT TYPE
RANGE LOW
12/00

Table 4-5 Analog Input Algorithm Selection

Range/Selections
Standard or Custom
Table 4-6 Standard Algorithm Prompts
Range/Selections
See Table 1-3 for selections. The
default type is OFF.
The value must be within the limits
specified for the input type (see Table
1-3). Be sure to use the correct value
for the temperature units used (°F, °C,
K, °R). To enter the full range for the
temperature units selected (see
TEMPERATURE UNITS), select TYPE
again and press Enter without changing
the range type.
VPR & VRX – User Manual
Programming Function Blocks and Features
Definition
This prompt appears only if "CUSTOM INPUT" is
enabled under Enable Features in the Program
Mode Menu (Section 4.19). If "CUSTOM INPUT"
is disabled you will see the Standard prompts
(Table 4-6).
Standard lets you choose a thermocouple, RTD,
EMF, or pyrometer type. The Standard prompts
are shown in Table 4-6.
Custom lets you convert the input from a
thermocouple or EMF to engineering units using a
custom curve containing up to 20 points.
Definition
Input type (thermocouple, RTD, pyrometer)
Low end of the input range.
85